94 Troubleshooting
3
Scroll down to the bottom, and click
Apply Changes
.
4
To make sure that a specific event is enabled, such as temperature warning,
select
Main System Chassis
from the tree view on the left.
5
Select
Temperatures
under
Main System Chassis
.
6
Select the
Alert Management
tab, and select
Temperature Probe Warning
.
7
Select the
Broadcast a Message
check box, and select
Apply Changes
.
8
To cause the temperature warning event, select
Main System Chassis
from
the tree view on the left.
9
Select
Temperatures
under
Main System Chassis
.
10
Select the
System Board Ambient Temp
link, and select the
Set to Values
radio button.
11
Set the
Maximum Warning Threshold
to
below
the current listed reading;
for example if the current reading is 27, set the threshold to 25.
12
Select
Apply Changes
,
and the temperature warning event is generated.
To cause another event, restore the original settings using the same
Set to
Valu es
option. Events are generated as warnings, and then to a normal
state.
If everything is working properly, navigate to the vCenter
Tasks & Events
tab, and select the
Events
view; a temperature probe warning event should
be displayed.
NOTE: There is a filter for duplicate events; if you try to trigger the same event
too many times in a row, you will only receive one event. Allow at least 30 seconds
between events to see all events.