• A/C Input Redundant — In this mode, the system is functional even if one PSU input circuit
stops functioning, provided the PSUs are connected to different input circuits. This is also
called AC redundancy.
• PSU Redundant — Available only on systems with four PSUs. This is also called DC
redundancy. This is only valid in a 2+1 PSU configuration. In this mode, the system is
functional even if one PSU stops functioning.
Default Value N/A
Write Privilege Login and configure iDRAC
License Required iDRAC7 Express or iDRAC7 Enterprise
Dependency None
NOTE: In a two PSU system, you must set the primary PSU (that must be ON). In a four PSU system, you must set
the pair of PSUs (1+3 or 2+4) that must be ON.
System.Power.Cap.Watts (Read or Write)
Description
Represents the Maximum Power in Watts a device is allowed to consume. To meet this capacity ,
throttle the device.
NOTE: This value is read only for Modular servers.
NOTE: This value is applicable only if System.Power.Cap.Enable is set to 1.
Legal Values
Values 0–100
Default Value
Server power threshold in watts
Write Privilege
Configure iDRAC
License
Required
iDRAC7 Express or iDRAC7 Enterprise
Dependency
Enable System.Power.Cap.Enable
System.Power.EnergyConsumption (Read Only)
Description
Represents the Cumulative power consumption by the blade or system.
Legal Values
Values: 1–65535
Default Value
Cumulative power consumption
Write Privilege
Configure iDRAC
License
Required
iDRAC7 Express or iDRAC7 Enterprise
Dependency
None